Serial number |
Fault line |
Trip time |
Inspection result |
Cause of failure |
Traveling wave positioning result |
Evaluation of positioning results |
1 |
HuaiPan Line |
2015/11/24 0:00 |
34# fiber is not enough distance to wire discharge
|
Noumenon
|
36#、39# |
accurate
|
2 |
TaiTai Line |
2016/1/17 15:21 |
Insulator flashing caused by bird droppings of B phase insulators in 11# tower
|
Bird damage
|
#11、#10 |
accurate |
3 |
TaiTai Line |
2016/1/19 20:43 |
Insulator flashing caused by bird droppings of B phase insulators in 11# tower
|
Bird damage |
#11、#12 |
accurate |
4 |
HuaiZhai Line |
2016/1/25 20:27 |
Insulator flashing caused by 45#A phase insulators bird droppings
|
Bird damage |
#45、#42 |
accurate |
5 |
HuaiPan Line |
2016/1/27 22:07 |
Insulator flashing caused by 60#B phase insulators bird droppings
|
Bird damage |
#60、#7 |
accurate |
6 |
HuaiZhai Line |
2016/1/29 14:59 |
Insulator flashing caused by 45#B phase insulators bird droppings
|
Bird damage |
#45、#42 |
accurate |
7 |
HuaiZhai Line |
2016/3/11 16:17 |
When 80#-81# built a house, the rope was on the wire
|
External rupture |
#78 |
accurate |